Type B DC Circuit Breaker vs. Leakage Protector: Don't Misuse Them in New Energy Scenarios! Detailed Differences & Functions
Overview details
|
DZ47-125DC Series Circuit Breaker |
DZ47-125DC |
|
|
Frame Degree Rated Current (A) |
125A |
|
|
Pole |
IP, 2P, 3R 4P |
|
|
Rated Operating Voltage (VDC) |
lP250\42P500\43P750\44P1000V |
|
|
Rated Current In (A) |
1,2,3,4,6,10,16,20,25,32,40,50,63,80,100,125 |
|
|
Rated Insulation Voltage Ui (VDC) |
1200VDC |
|
|
Rated Impact Voltage Uimp (kV) |
4kV |
|
|
Ultimate Breaking Capacity leu (kA) |
4.5kA/6kA |
|
|
Run Breaking Capacity les (%lcu) |
75% |
|
|
Curve Type |
C |
|
|
Trip Type |
Thermal-magnetic |
|
|
Mechanical Life |
Actual Average Value |
20000 |
|
|
Standard Value |
8500 |
|
Electric Life |
Actual Average Value |
6000 |
|
|
Standard Value |
2500 |
overcurrent. When the current flowing through a circuit exceeds the rated current of the MCB, it will automatically trip and break the circuit. This prevents the wires and electrical components in the circuit from overheating and potentially causing a fire. For example, in a household electrical circuit, if too many appliances are connected and the total current draw exceeds the capacity of the MCB, it will quickly act to cut off the power and protect the circuit.
The MCB also provides short-circuit protection. In the event of a short circuit, where a direct connection between the live and neutral wires occurs, the MCB will immediately trip to stop the extremely high current from flowing. This rapid response helps to protect the electrical system from serious damage that could be caused by a short-circuit event.
Another important role of the MCB is to enable easy control and isolation of individual circuits. It can be manually switched off to disconnect a particular circuit for maintenance or repair work without affecting the other circuits in the system. This makes it convenient for electricians to work on specific parts of the electrical installation.
Moreover, MCBs are often designed with a compact size, making them suitable for installation in a variety of settings, including residential buildings, commercial spaces, and small industrial applications. They are an essential part of the electrical distribution system, ensuring the safety and proper operation of electrical circuits and protecting both people and property from the risks of electrical faults.
Engineered with precision and reliability at its core, this circuit breaker adheres to the stringent guidelines outlined in the IEC60898 standard. This adherence signifies its commitment to safety, efficiency, and compatibility with international norms, ensuring that it not only meets but exceeds expectations in performance and durability. Its design philosophy revolves around safeguarding circuits from overloads and short circuits, thereby acting as a vigilant protector of your electrical systems.
Moreover, the circuit breaker's construction is a testament to advanced engineering, incorporating state-of-the-art components that enhance its performance in diverse environmental conditions. Whether it's the rigorous demands of industrial settings or the precise requirements of residential installations, this circuit breaker stands as a reliable solution, offering peace of mind and ensuring that electrical systems operate smoothly and safely.
In summary, this circuit breaker, designed for a 125A rated current and available in multiple pole configurations, is an essential component for lighting and distribution systems across various sectors. Its compliance with the IEC60898 standard and its robust design make it a top-tier choice for safeguarding electrical systems in industrial, commercial, and residential environments.
Technieal Sepcifcation
|
Wiring Capacity (mm2) |
32A, 1~25 mm2J^40A, 10~35mm2 |
||||
|
Ambient Temperature (*C) |
-20-+70 |
||||
|
Altitude |
^2000 |
||||
|
Relative Humidity |
W95% |
||||
|
Pollution Level |
3 |
||||
|
Installation Environment |
No obvious shock and vibration |
||||
|
Installation Category |
Class III |
||||
|
Installation |
DIN Standard rail |
||||
|
Dimensions(W)x(H)x(Deep) |
W |
18 |
36 |
54 |
72 |
|
|
H |
80 |
80 |
80 |
80 |
|
|
c |
71 |
71 |
71 |
71 |
|
Weight (kg) |
0.12 |
0.24 |
0.36 |
0.48 |
|

description2
FAQ
-
1. Can our company protect the privacy of our customers?
-
2. how can we guarantee quality?





