How should one address excessively high operating temperatures in a photovoltaic combiner box?
I have encountered the issue of abnormal temperatures in Combiner Boxes far too often. During my routine inspections, I use an infrared thermal scanner to check the units, and I frequently find the surface temperature of the enclosure soaring to 70 or 80 degrees Celsius—it’s truly scalding to the touch.
Generally speaking, a somewhat high internal temperature within a piece of equipment does not necessarily constitute a major incident; however, if the temperature rises to the point where terminal blocks become discolored, or if wisps of smoke begin to appear near the fuses, then immediate action must be taken to address the situation.
Today, I’d like to share with you the pitfalls we’ve encountered during our hands-on field operations over the years, along with the comprehensive set of solutions we’ve developed to address them. My goal is to ensure that if you run into these same issues in the future, you won’t be left scrambling or feeling at a complete loss as to what to do.
Why do photovoltaic combiner boxes heat up?
To put it plainly, the reasons boil down to just a few possibilities. The most common issue is that a terminal hasn’t been tightened properly; when current flows through it, the contact resistance becomes very high, causing that specific point to generate an intense amount of heat—which, in turn, sends the temperature inside the entire enclosure soaring.
If you examine old power plants that haven’t undergone maintenance for two or three years, you’ll often find screws that have come loose or oxidized—a quick touch is all it takes to get a clear sense of the situation. Another possibility is that a diode has failed or a fuse has a poor connection, forcing the current to take a bypass route; this causes heat to accumulate in that specific spot, with no way for it to dissipate.

Environmental factors must also not be overlooked. During the height of summer, photovoltaic (PV) panels become extremely hot under the sun. Since combiner boxes are often installed directly beneath these panels—in areas lacking ventilation—the temperature inside a combiner box can end up being more than a dozen degrees higher than the ambient air temperature.
Furthermore, the load was underestimated during the design phase; in reality, the number of connected lines exceeds the rated capacity, causing the current to consistently operate at its absolute limit. Consequently, it is impossible to keep the temperature under control. Typically, these factors occur in combination.
How to investigate high temperatures in a PV combiner box?
Once on-site, avoid making wild guesses; instead, use an infrared thermometer to scan the components one by one. I typically start from the top of the electrical panel and work my way down, looking for the point with the highest temperature—that spot is very likely where the fault lies.
Focus your attention on the fuse holders and terminal blocks along each circuit, and observe whether the surface temperature of any component is significantly higher than that of the surrounding areas. If a noticeable temperature difference is detected, that specific circuit should be prioritized for inspection. Experienced technicians may also gently touch the components with the back of their hand to gauge the heat; if the temperature difference feels like it exceeds ten degrees or more, it is a sign that something is amiss.
Once the temperature measurement is complete, open the cover to inspect the components. Check for any signs of discoloration or ablation on the terminals, ensure that the wire lugs are not loose (i.e., that the threads have not stripped), and examine the fuses for any bulging or blackening. If no obvious issues are visible upon inspection, use a clamp meter to measure the current in each circuit; look for any circuits where the current is excessively high, or for any current imbalance between the three phases.
I once encountered a specific case where a short circuit occurred in a circuit string, causing the current to spike to its maximum limit. The terminal block for that circuit became so intensely hot—hot enough, in fact, to fry an egg—yet, from the outside, everything appeared perfectly fine. Without using instruments to measure the current, it would have been extremely difficult to detect the underlying problem.
How to address overheating in a PV combiner box?
Once the source of the problem has been identified, the actual repair process is generally straightforward. For any loose wiring terminals, first ensure that the power supply has been disconnected. Then, using a torque wrench, retighten the connections—strictly adhering to the torque specifications provided by the manufacturer—to ensure that every screw is tightened to the required level.
If the oxidation is severe, the terminals should be removed and their surfaces thoroughly sanded clean before being reinstalled; this typically results in a significant reduction in contact resistance.

If you discover that a diode component or a fuse has burned out or become damaged, you should replace it with a brand-new part of the exact same model. Be sure to avoid purchasing such components from unofficial or unreliable sources; products obtained through these channels often lack quality assurance and are highly likely to fail again after only two months of use.
If the load indeed exceeds the limit, consider relocating some of the excess strings to other combiner boxes; if that is not feasible, add a bypass circuit. In locations with poor heat dissipation, a temperature-controlled fan can be installed inside the enclosure to improve ventilation. This modification costs approximately 100 to 200 RMB and can reduce the temperature by about 15 to 16 degrees Celsius.
One of the most extreme cases I have personally handled involved an enclosure packed with 48 signal lines or circuits; during the high temperatures of summer, the internal temperature soared to over 90 degrees Celsius. The only way to fully resolve this issue was to replace the unit with a new, larger-capacity enclosure.
Do not delay in addressing the issue of excessive temperatures. If left unaddressed, the consequences can vary significantly: at best, it accelerates the aging of insulation materials, thereby shortening the equipment's service life; at worst, it could cause terminals to melt or even lead to a fire within the enclosure, resulting in a complete shutdown of the power station. Therefore, during routine inspections, it is highly recommended to capture multiple infrared thermal images for analysis. Should any abnormal temperatures be detected, do not wait for them to rise further—resolve the issue that same day. Establishing this as a standardized, routine procedure is far more manageable and reliable than scrambling for emergency repairs after a failure has already occurred.
Chang Song Electric Co., Ltd. The company is a high-tech enterprise specializing in electrical equipment for photovoltaic power generation systems. Since its inception, it has focused on meeting the core demands of the new energy sector. Leveraging solid technical expertise and innovation capabilities, the company has established a comprehensive business system covering the entire spectrum of electrical equipment for photovoltaics, while continuously optimizing product performance and service processes to address the specific operational requirements of photovoltaic power generation environments.
Changsong Electric is dedicated to providing global customers with safe, efficient, and intelligent electrical connection and protection solutions. Backed by professional technical support and comprehensive service capabilities, the company has established stable partnerships and a strong brand reputation in both domestic and international new energy markets, thereby contributing to the safe, efficient, and intelligent development of the global photovoltaic industry.