How should DC circuit breakers for photovoltaic combiner boxes be selected?
I have consulted well over a hundred sets of drawings regarding the selection of circuit breakers for PV combiner boxes. Many newcomers to the industry find themselves conFused whenever they encounter issues on the DC side—whereas, on the inverter side, the parameters are typically specified with great clarity.
However, when it comes to combiner boxes, it’s not always clear how to select the right circuit breaker. To put it plainly, there are only three core factors to consider. First is the rated current—make sure it’s not too low. Second is the breaking capacity—again, ensure it’s not too low. Third is the coordination of protection grading—this must be done correctly. Let’s skip the unnecessary filler and get straight to the specifics.
How to calculate the selection of a photovoltaic (PV) circuit breaker
The most fundamental step is to calculate the maximum operating current for a string of modules. To do this, take the short-circuit current ($I_{SC}$) value from the module's datasheet and multiply it by a temperature correction factor of 1.1; the resulting figure represents the maximum current within a single circuit.
For example, if the $I_{SC}$ (short-circuit current) value of a specific module is 12.5 amperes, multiplying this by 1.1 yields 13.75 amperes. As another example, if a series configuration—consisting of ten circuits—feeds into a combiner box, the maximum allowable current for the busbar would be 137.5 amperes.
The rated current of the circuit breaker must be higher than this value; however, you cannot simply choose an 800-amp high-capacity circuit breaker, as doing so would compromise the sensitivity of the protection.

In engineering practice, it is standard to select a value 1.25 to 1.5 times the calculated current; based on this, the required capacity is over 137.5 amperes, making a 200-ampere rating an appropriate choice. Regarding breaking capacity, the requirements for the DC side are more stringent than those for the AC side; for a 600-volt DC system, one must select a device with a breaking capacity of at least 6 kA. If the voltage is higher, a product with a correspondingly higher breaking capacity is required.
What size circuit breaker is sufficient for a combiner box?
A common misconception among most people is the failure to account for the significant heat generated by bypass diodes. When a photovoltaic module is partially shaded, the affected solar cells instantly lose their power-generating capacity and instead become electrical loads. Consequently, the entire current flowing through the circuit is forced to pass through the bypass diodes, causing their temperature to spike—often exceeding the critical threshold of 150°C.
If you base your selection and design solely on standard operating conditions—without accounting for this thermal effect—then any incidental occurrence, such as bird droppings covering the equipment or the casting of shadows from trees, will trigger the internal thermal protection switch. This will immediately cut off the power, causing the entire sub-array to lose power and become completely inoperative.
To my knowledge, two specific projects in the Xinjiang region experienced frequent accidents precisely due to this chain of cause and effect; in particular, during the summer months, the accumulation of bird droppings on the panels occurred far more often than is typically assumed—a reality that is generally underestimated.

Therefore, when selecting equipment, it is essential to account for the ambient temperature correction factor. This is a critical step, as equipment operating in high-temperature environments often requires a correction factor of 0.85 or even lower. This means that even if two units have the same nominal rated current, their actual current-carrying capacity can be significantly reduced. Another detail to keep in mind concerns combiner boxes where multiple circuits share a single main circuit breaker: when calculating the total current, do not assume that every circuit is operating at its maximum output simultaneously. Instead, apply a simultaneity factor of 0.8. Failing to do so will result in the selection of an unnecessarily oversized component—a mistake that not only leads to wasted costs but also consumes extra space.
Key Points for DC-Side Circuit Breaker Calculation
Let’s now discuss two areas where accidents are particularly likely to occur. Direct current (DC) arcs and alternating current (AC) arcs are fundamentally different; because a DC arc never passes through a zero-current point, it cannot extinguish itself. This means that the breaking capacity of a DC circuit breaker must be precisely matched to the DC voltage level of the system.
If you were to use a circuit breaker with a 600V rating in a 2000V DC system, an electrical arc could potentially burn through and completely destroy all the combiner boxes. Furthermore, it is important to consider the concept of "coordination" (or grading) between protective devices: within a combiner box, there is typically a designated difference in rating—or a "step"—between the branch circuit breakers and the main circuit breaker.
For example, the branch circuit breakers might be set with a rated current of 63 amperes, while the main circuit breaker is set to 160 amperes. This configuration ensures that if a fault occurs on a branch circuit, the corresponding branch circuit breaker will trip first. Such a design effectively prevents "nuisance" or "upstream" tripping—where a breaker further up the line trips unnecessarily—thereby avoiding an unintended power cut to the entire series-connected circuit.
Before issuing any set of drawings, I always verify them against the actual project data—never just rely on plugging numbers into formulas.
Selecting a circuit breaker that is too small for the application can lead to, at best, nuisance tripping—which disrupts power generation—and, at worst, the formation of DC arcs or even the destruction of the distribution box. The meager savings of a few dozen yuan on the cost of the circuit breaker could ultimately result in liabilities and compensation payments reaching hundreds of thousands of yuan.
Chang Song Electric Co., Ltd. The company is a high-tech enterprise specializing in electrical equipment for photovoltaic power generation systems. Since its inception, it has focused on meeting the core demands of the new energy sector. Leveraging solid technical expertise and innovation capabilities, the company has established a comprehensive business system covering the entire spectrum of electrical equipment for photovoltaics, while continuously optimizing product performance and service processes to address the specific operational requirements of photovoltaic power generation environments.
Changsong Electric is dedicated to providing global customers with safe, efficient, and intelligent electrical connection and protection solutions. Backed by professional technical support and comprehensive service capabilities, the company has established stable partnerships and a strong brand reputation in both domestic and international new energy markets, thereby contributing to the safe, efficient, and intelligent development of the global photovoltaic industry.