220kv three-phase oil-immersed on-load voltage regulating transformer Oil Transformer
Overview details
220kv three-phase oil-immersed on-load tap-changing transformer has brought a series of major changes in materials, technology, structure, etc. It is characterized by compact structure, light weight, high efficiency, low loss, low noise and reliable performance. This product can greatly reduce power grid loss and operating costs, and has significant economic benefits.
The products comply with the following national standards: GB1094.1-2013 Power transformers Part 1: General; GB1094.2-2013 Power transformers Part 2. Temperature rise; GB1094.3-2003 Power transformers Part 3: Insulation levels, dielectric tests and external tolerance in air; GB1094.5-2003 Power transformers Part 5: Short-circuit withstand capability; GB/6451-2015 Specifications and technical requirements for three-phase oil-immersed power transformers.
Technical parameter
|
220kv three-phase oil-immersed on-load voltage regulating transformer |
|||||||
|
Rated capacity |
Voltage Group |
Vector set |
No-load loss |
Load loss |
No-load current |
Short circuit impedance |
|
|
high pressure |
Low pressure |
kW |
kW |
% |
|||
|
31500 |
|
6.3 |
YNd11 |
28 |
128 |
0.56 |
12-14 |
|
40000 |
|
32 |
149 |
0.56 |
|||
|
50000 |
|
39 |
179 |
0.52 |
|||
|
63000 |
|
46 |
209 |
0.52 |
|||
|
75000 |
|
10.5 |
53 |
237 |
0.48 |
||
|
90000 |
|
64 |
273 |
0.44 |
|||
|
120000 |
|
75 |
338 |
0.44 |
|||
|
150000 |
220±2*2.5% |
10.5,11,13.8 |
89 |
400 |
0.40 |
||
|
160000 |
242±2*2.5% |
15.75 |
93 |
420 |
0.39 |
||
|
180000 |
|
18,20 |
102 |
459 |
0.36 |
||
|
240000 |
|
|
128 |
538 |
0.33 |
||
|
300000 |
|
13.8 |
154 |
641 |
0.30 |
||
|
360000 |
|
17 |
735 |
0.30 |
|||
|
370000 |
|
176 |
750 |
0.30 |
|||
|
400000 |
|
187 |
795 |
0.28 |
|||
|
420000 |
|
193 |
824 |
0.28 |
|||
Note 2: 35 kV or 38.5 kV low voltage transformers can also be provided upon request.
Note 3: A non-split structure is preferred. Sub-connectors may be provided if necessary.
Note 4: When the annual average load rate of the transformer is between 45% and 50%, the loss value in the table can be used to calculate the maximum operating efficiency.
description2
FAQ
-
1.What are our main products?
Primary and secondary equipment prefabrication compartment, photovoltaic booster substation, photovoltaic grid-connected cabinet, parallel cage, PV combiner box, MCCB,MCB,The surge protector,tec. -
2. If I go to China, can I visit your factory?
-
3. Can the product be used in harsh environments?